Round Teck International Company(Wire Series,Electronic Wire

UL 1032/CSA TR-32High Voltage Hook-up Wire

Internal wiring of electrical equipment.
 
Specifications
1.Conductor:Annealed Copper Wire,(Bare Single,Tinned Single, Tinned Strand,or Top-Tinned Strand)
2.Insulation: PVC (Polyvinyl Chloride)3.Structure:




Conductor

Insulation

Conductor Resistance(20℃)


AWG

Construction

Diameter

Min Thickness

Nominal Thickness

Diameter


24

11 / 0.16TA

approx.0.61 mm

0.686 mm

0.795 mm

2.20 ± 0.10 mm

85.49W / Km


24

7 / 0.20TA

approx.0.60 mm

0.80 mm

2.20 ± 0.10 mm

85.95W / Km


22

17 / 0.16TA

approx.0.76 mm

0.82 mm

2.40 ± 0.10 mm

59.74W / Km


22

7 / 0.26TA

approx.0.78 mm

0.81 mm

2.40 ± 0.10 mm

54.79W / Km


20

21 / 0.18TA

approx.0.95 mm

0.875 mm

2.70 ± 0.10 mm

38.46W / Km


20

7 / 0.32TA

approx.0.96 mm

0.87 mm

2.70 ± 0.10 mm

34.12W / Km


20

10 / 0.26TA

approx.0.95 mm

0.875 mm

2.70 ± 0.10 mm

38.71W / Km


18

34 / 0.18TA

approx.1.20 mm

0.845 mm

2.90 ± 0.10 mm

24.70W / Km


20

1 / 0.813TA

approx.0.813 mm

0.843 mm

2.50 ± 0.10 mm

35.20W / Km


22

7 / 0.26ATC

approx.0.76 mm

0.81 mm

2.40 ± 0.10 mm

57.30W / Km
A:Bare Copper B:Tinned Copper ATC:Top-Tinned Strand
 
4.Characteristics:




Items

Specification


Rating

90℃ 1000V(AC) , 1200V(DC)


Dielectric Strength

AC 3000V / min.


Insulation Resistance

Min. 10MW - Km (20℃) at DC 500V


Flame Test

UL:VW-1 CSA:FT-1


Elongation of Insulation

Min.100 ﹪


Tensile Strength of Insulation

Min.1.05Kg / mm2


Residual of Elongation after Aging

Min. 65 ﹪of original (113℃,168H)


Residual of Tensile Strength after Aging

Min. 70 ﹪of original (113℃,168H)
 
5.Marking:E54979 AWM 1032 VW - 1 1000V (AC) 1200V(DC) 90℃ □AWG TATUNG LL58500 CSA TR - 32 FT1 - F -