UL 1032/CSA TR-32High Voltage Hook-up Wire
Internal wiring of electrical equipment.
Specifications
1.Conductor:Annealed Copper Wire,(Bare Single,Tinned Single, Tinned Strand,or Top-Tinned Strand)
2.Insulation: PVC (Polyvinyl Chloride)3.Structure:
Conductor
Insulation
Conductor Resistance(20℃)
AWG
Construction
Diameter
Min Thickness
Nominal Thickness
Diameter
24
11 / 0.16TA
approx.0.61 mm
0.686 mm
0.795 mm
2.20 ± 0.10 mm
85.49W / Km
24
7 / 0.20TA
approx.0.60 mm
0.80 mm
2.20 ± 0.10 mm
85.95W / Km
22
17 / 0.16TA
approx.0.76 mm
0.82 mm
2.40 ± 0.10 mm
59.74W / Km
22
7 / 0.26TA
approx.0.78 mm
0.81 mm
2.40 ± 0.10 mm
54.79W / Km
20
21 / 0.18TA
approx.0.95 mm
0.875 mm
2.70 ± 0.10 mm
38.46W / Km
20
7 / 0.32TA
approx.0.96 mm
0.87 mm
2.70 ± 0.10 mm
34.12W / Km
20
10 / 0.26TA
approx.0.95 mm
0.875 mm
2.70 ± 0.10 mm
38.71W / Km
18
34 / 0.18TA
approx.1.20 mm
0.845 mm
2.90 ± 0.10 mm
24.70W / Km
20
1 / 0.813TA
approx.0.813 mm
0.843 mm
2.50 ± 0.10 mm
35.20W / Km
22
7 / 0.26ATC
approx.0.76 mm
0.81 mm
2.40 ± 0.10 mm
57.30W / Km
A:Bare Copper B:Tinned Copper ATC:Top-Tinned Strand
4.Characteristics:
Items
Specification
Rating
90℃ 1000V(AC) , 1200V(DC)
Dielectric Strength
AC 3000V / min.
Insulation Resistance
Min. 10MW - Km (20℃) at DC 500V
Flame Test
UL:VW-1 CSA:FT-1
Elongation of Insulation
Min.100 ﹪
Tensile Strength of Insulation
Min.1.05Kg / mm2
Residual of Elongation after Aging
Min. 65 ﹪of original (113℃,168H)
Residual of Tensile Strength after Aging
Min. 70 ﹪of original (113℃,168H)
5.Marking:E54979 AWM 1032 VW - 1 1000V (AC) 1200V(DC) 90℃ □AWG TATUNG LL58500 CSA TR - 32 FT1 - F -