600V~25kV Cross-Linked Polyethylene Insulated, steel wires armor and Low-Smoke and Halogen-Free (LSHF) Compound Jacketed Power Cables. It is used at wiring for power distribution system. The power cables shall comply with the standard of IEC 60502.
Features
Construction:(1) Conductor: untinned soft annealed stranded or solid copper wires (2) Conductor screen (voltage >2001V) (3) Insulation: XLPE. (4) Insulation screen (voltage > 2001V) (5) Copper tape shielding (voltage > 2001V) (6) Two or more cores are twisted together,cable core covered with proper separator (7) Inner Sheath: LSHF (8) Steel wires armor (9) Sheath: LSHF Introduction: 600V~25kV Cross-Linked Polyethylene Insulated, steel wires armor, Low-Smoke and Halogen-Free (LSHF) Compound Jacketed Power Cables (CL-SWA). It has following characteristics: (1) Low toxicity index; per NES 713; toxicity index <=5 (2) Don’t produce halogen gas; per IEC 60754-1; Amount of HCL gas <=0.5% (3) Low smoke; LSHF compound per ASTM E662 smoke density test; Ds<=250,VOF4<=100 (4) Excellent flame resistance; per ASTM D2863 oxygen index; OI >=30; per IEEE 383 vertical open tray flame test; passed. The Low-Smoke and Halogen-Free (LSHF) wire and cable could minimize the lowest damage in case of fire. Therefore, the public areas, such as subway, tunnel, railway, public building, substreet, ships, power stations, school, hospital, and rapid transit system in more suitable to install the LSHF cable to secure the human lives and properties.
Specifications
600V XLPE insulated, steel wire armor, LSHF sheathed cables 1C (CL-SWA)
Conductor
Thickness of insulation
mm
Approx.Overall Diameter
mm
Approx.
Weight
Kg/km
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer DiameterApprox.
mm
-
1/1.0
1.0
0.7
9.9
160
-
1/1.2
1.2
0.7
10.1
170
-
1/1.6
1.6
0.7
10.5
190
-
1/2.0
2.0
0.7
10.9
215
-
1/2.6
2.6
0.7
11.5
250
-
1/3.2
3.2
0.7
12.1
290
2
7/0.6
1.8
0.7
10.7
195
1.25
7/0.45
1.35
0.7
10.4
165
3.5
7/0.8
2.4
0.7
11.3
225
5.5
7/1.0
3.0
0.7
11.9
265
8
7/1.2
3.4
0.7
12.3
300
14
7/1.6
4.4
0.7
13.3
385
22
7/2.0
5.5
0.7
14.4
490
30
7/2.3
6.4
0.9
15.9
605
38
7/2.6
7.3
0.9
16.8
715
50
19/1.8
8.4
1.0
18.2
860
60
19/2.0
9.3
1.0
19.1
995
80
19/2.3
10.7
1.1
22.5
1495
100
19/2.6
12.0
1.1
23.8
1755
125
19/2.9
13.5
1.2
25.5
2075
150
37/2.3
14.7
1.4
27.3
2435
200
37/2.6
17.0
1.6
30.2
2990
250
61/2.3
19.0
1.7
33.6
3870
325
61/2.6
21.7
1.8
36.8
4735
400
61/2.9
24.1
2.0
40.0
5690
500
61/3.2
26.9
2.2
41.1
6740
600V XLPE insulated, steel wire armor, LSHF sheathed cables 2C (CL-SWA)
Conductor
Thickness of insulation
mm
Approx.Overall Diameter
mm
Approx.
Weight
Kg/km
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer DiameterApprox.
mm
-
1/1.0
1.0
0.7
13.0
265
-
1/1.2
1.2
0.7
13.3
281
-
1/1.6
1.6
0.7
14.1
325
-
1/2.0
2.0
0.7
15.0
380
-
1/2.6
2.6
0.7
16.4
470
-
1/3.2
3.2
0.7
17.6
564
2
7/0.6
1.8
0.7
14.7
350
1.25
7/0.45
1.35
0.7
13.9
295
3.5
7/0.8
2.4
0.7
16.0
420
5.5
7/1.0
3.0
0.7
17.1
500
8
7/1.2
3.4
0.7
18.0
575
14
7/1.6
4.4
0.7
20.1
770
22
7/2.0
5.5
0.7
24.0
1295
30
7/2.3
6.4
0.9
26.7
1590
38
7/2.6
7.3
0.9
29.7
1945
50
19/1.8
8.4
1.0
31.6
2255
60
19/2.0
9.3
1.0
34.6
2830
80
19/2.3
10.7
1.1
38.0
3435
100
19/2.6
12.0
1.1
41.1
4070
125
19/2.9
13.5
1.2
46.0
5220
150
37/2.3
14.7
1.4
49.3
6070
200
37/2.6
17.0
1.6
55.6
7455
250
61/2.3
19.0
1.7
60.6
9035
325
61/2.6
21.7
1.8
67.4
10885
400
61/2.9
24.1
2.0
73.6
14060
500
61/3.2
26.9
2.2
81.3
15660
600V XLPE insulated, steel wire armor, LSHF sheathed cables 3C (CL-SWA)
Conductor
Thickness of insulation
mm
Approx.Overall Diameter
mm
Approx.
Weight
Kg/km
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer DiameterApprox.
mm
-
1/1.0
1.0
0.7
13.4
285
-
1/1.2
1.2
0.7
13.8
310
-
1/1.6
1.6
0.7
14.9
370
-
1/2.0
2.0
0.7
15.7
445
-
1/2.6
2.6
0.7
17.0
545
-
1/3.2
3.2
0.7
18.3
665
2
7/0.6
1.8
0.7
15.3
390
1.25
7/0.45
1.35
0.7
14.3
325
3.5
7/0.8
2.4
0.7
16.6
480
5.5
7/1.0
3.0
0.7
17.9
580
8
7/1.2
3.4
0.7
18.7
685
14
7/1.6
4.4
0.7
22.7
1200
22
7/2.0
5.5
0.7
25.1
1555
30
7/2.3
6.4
0.9
28.1
1945
38
7/2.6
7.3
0.9
30.2
2295
50
19/1.8
8.4
1.0
34.5
3040
60
19/2.0
9.3
1.0
36.7
3500
80
19/2.3
10.7
1.1
40.5
4325
100
19/2.6
12.0
1.1
43.6
5190
125
19/2.9
13.5
1.2
48.7
6600
150
37/2.3
14.7
1.4
52.7
7720
200
37/2.6
17.0
1.6
59.4
9610
250
61/2.3
19.0
1.7
64.5
11725
325
61/2.6
21.7
1.8
71.8
14510
400
61/2.9
24.1
2.0
79.9
18420
500
61/3.2
26.9
2.2
87.9
21930
600V XLPE insulated, steel wire armor, LSHF sheathed cables 4C (CL-SWA)
Conductor
Thickness of insulation
mm
Approx.Overall Diameter
mm
Approx.
Weight
Kg/km
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer DiameterApprox.
mm
-
1/1.0
1.0
0.7
14.1
320
-
1/1.2
1.2
0.7
14.7
355
-
1/1.6
1.6
0.7
15.7
425
-
1/2.0
2.0
0.7
16.7
500
-
1/2.6
2.6
0.7
18.1
635
-
1/3.2
3.2
0.7
19.6
785
2
7/0.6
1.8
0.7
16.2
405
1.25
7/0.45
1.35
0.7
15.1
365
3.5
7/0.8
2.4
0.7
17.4
555
5.5
7/1.0
3.0
0.7
19.1
680
8
7/1.2
3.4
0.7
20.3
815
14
7/1.6
4.4
0.7
24.3
1420
22
7/2.0
5.5
0.7
27.1
1890
30
7/2.3
6.4
0.9
30.5
2370
38
7/2.6
7.3
0.9
33.8
3055
50
19/1.8
8.4
1.0
37.3
3705
60
19/2.0
9.3
1.0
39.9
5395
80
19/2.3
10.7
1.1
45.3
5825
100
19/2.6
12.0
1.1
48.8
6895
125
19/2.9
13.5
1.2
53.5
8195
150
37/2.3
14.7
1.4
57.8
9690
200
37/2.6
17.0
1.6
64.9
12015
250
61/2.3
19.0
1.7
70.8
14780
325
61/2.6
21.7
1.8
80.5
19260
400
61/2.9
24.1
2.0
87.9
23195
500
61/3.2
26.9
2.2
96.6
27620