600V~25KV Cross-Linked Polyethylene Insulated and Polyvinyl Chloride Sheathed Cables. It is used at wiring for power and equipment. The cables shall comply with the standard of CNS 2655.
Features
Construction:(1) Conductor: untinned soft annealed stranded or solid copper wires (2) Conductor screen (voltage >2001V) (3) Insulation: XLPE. (4) Insulation screen (voltage > 2001V) (5) Copper tape shielding (voltage > 2001V) (6) Two or more cores are twisted together,cable core covered with proper separator (7) Sheath: PVC Introduction: Signed technical cooperation with “Furukawa Denko K.K. Japan” to produce XLPE cable in 1967. Signed technical cooperation with “Furukawa Denko K.K. Japan” to produce 33KV XLPE cable in 1977. In 1977, we invested heavily in strippable insulation screen with three tandem extrusions. In 1985, we developed dry curing method for insulated process. 600V~25KV XLPE power cable has labeled our National Quality Standard.
Specifications
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
600V One Core
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
-
1/1.6
1.6
0.76
4.2
49
300
-
1/2.0
2.0
0.76
4.6
63
300
-
1/2.6
2.6
0.76
4.9
87
300
-
1/3.2
3.2
1.14
6.7
128
300
2.0
7/0.6
1.8
0.76
4.4
51
300
3.5
7/0.8
2.4
0.76
5.0
71
300
5.5
7/1.0
3.0
0.76
5.6
94
300
8
7/1.2
3.6
1.14
6.6
134
300
14
7/1.6
4.8
1.14
8.6
203
300
22
7/2.0
6.0
1.14
9.8
288
300
38
7/2.6
7.8
1.40
12.1
450
300
60
19/2.0
10.0
1.40
15.6
679
300
100
19/2.6
13.0
1.40
18.5
1083
300
150
37/2.3
16.1
1.65
23.4
1676
300
200
37/2.6
18.2
1.65
25.5
2091
200
250
61/2.3
20.7
1.65
28.0
2665
200
325
61/2.6
23.4
2.03
31.4
3380
200
400
61/2.9
26.1
2.03
34.1
4147
200
500
61/3.2
28.8
2.03
36.8
4990
150
600
91/2.9
31.9
2.41
38.5
6105
150
800
127/2.8
36.4
2.41
46.9
7883
150
1000
127/3.2
41.6
2.41
52.1
10160
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
600V Two Cores
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
-
1/1.6
1.6
0.76
9.4
110
300
-
1/2.0
2.0
0.76
10.2
140
300
-
1/2.6
2.6
0.76
11.4
195
300
-
1/3.2
3.2
1.14
14.4
322
300
2.0
7/0.6
1.8
0.76
9.8
116
300
3.5
7/0.8
2.4
0.76
11.0
160
300
5.5
7/1.0
3.0
0.76
12.2
213
300
8
7/1.2
3.6
1.14
16.0
341
300
14
7/1.6
4.8
1.14
18.4
502
300
22
7/2.0
6.0
1.14
20.8
699
300
38
7/2.6
7.8
1.40
26.6
927
300
60
19/2.0
10.0
1.40
31.0
1683
300
100
19/2.6
13.0
1.40
36.8
2615
300
150
37/2.3
16.1
1.65
46.3
4053
300
200
37/2.6
18.2
1.65
50.3
5003
300
250
61/2.3
20.7
1.65
55.3
6313
200
325
61/2.6
23.4
2.03
62.1
7985
200
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
600V Three Cores
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
-
1/1.6
1.6
0.76
9.9
135
300
-
1/2.0
2.0
0.76
10.8
177
300
-
1/2.6
2.6
0.76
12.1
253
300
-
1/3.2
3.2
1.14
16.1
414
300
2.0
7/0.6
1.8
0.76
10.4
142
300
3.5
7/0.8
2.4
0.76
11.6
200
300
5.5
7/1.0
3.0
0.76
12.9
272
300
8
7/1.2
3.6
1.14
17.0
431
300
14
7/1.6
4.8
1.14
19.5
649
300
22
7/2.0
6.0
1.14
25.1
971
300
38
7/2.6
7.8
1.40
28.3
1533
300
60
19/2.0
10.0
1.40
33.0
2271
300
100
19/2.6
13.0
1.40
39.3
3604
300
150
37/2.3
16.1
1.65
49.4
5560
300
200
37/2.6
18.2
1.65
53.7
6907
200
250
61/2.3
20.7
1.65
59.1
8769
200
325
61/2.6
23.4
2.03
66.5
11120
200
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
600V Four Cores
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
-
1/1.6
1.6
0.76
10.7
166
300
-
1/2.0
2.0
0.76
11.7
219
300
-
1/2.6
2.6
0.76
13.1
317
300
-
1/3.2
3.2
1.14
16.8
488
300
2.0
7/0.6
1.8
0.76
11.2
174
300
3.5
7/0.8
2.4
0.76
12.7
252
300
5.5
7/1.0
3.0
0.76
14.9
373
300
8
7/1.2
3.6
1.14
18.5
545
300
14
7/1.6
4.8
1.14
22.4
885
300
22
7/2.0
6.0
1.14
25.3
1251
300
38
7/2.6
7.8
1.40
31.1
1960
300
60
19/2.0
10.0
1.40
36.4
2943
300
100
19/2.6
13.0
1.40
45.1
4845
300
150
37/2.3
16.1
1.65
54.5
7191
200
200
37/2.6
18.2
1.65
59.4
8961
200
250
61/2.3
20.7
1.65
65.4
11400
200
325
61/2.6
23.4
2.03
75.2
14760
200
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
601~2000V One Core
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
2.0
7/0.6
1.8
1.14
7.3
56
300
3.5
7/0.8
2.4
1.14
7.9
74
300
5.5
7/1.0
3.0
1.14
8.4
98
300
8
7/1.2
3.6
1.40
9.6
133
300
14
7/1.6
4.8
1.40
11.6
200
300
22
7/2.0
6.0
1.40
12.8
284
300
38
7/2.6
7.8
1.65
15.6
451
300
60
19/2.0
10.0
1.65
18.6
690
300
100
19/2.6
13.0
1.65
21.6
1098
300
150
37/2.3
16.1
1.90
26.3
1692
300
200
37/2.6
18.2
1.90
28.4
2111
300
250
61/2.3
20.7
1.90
30.9
2669
200
325
61/2.6
23.4
2.29
34.4
3391
200
400
61/2.9
26.1
2.29
37.1
4154
200
500
61/3.2
28.8
2.29
39.7
4996
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
601~2000V Three Cores
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
2.0
7/0.6
1.8
1.14
13.8
179
300
3.5
7/0.8
2.4
1.14
15.0
241
300
5.5
7/1.0
3.0
1.14
18.0
348
300
8
7/1.2
3.6
1.40
20.5
473
300
14
7/1.6
4.8
1.40
23.0
698
300
22
7/2.0
6.0
1.40
28.0
1040
300
38
7/2.6
7.8
1.65
32.8
1615
300
60
19/2.0
10.0
1.65
37.5
2363
300
100
19/2.6
13.0
1.65
44.0
3703
300
125
19/2.9
14.5
1.90
51.8
4751
200
150
37/2.3
16.1
1.90
55.3
5671
200
200
37/2.6
18.2
1.90
60.0
7039
150
250
61/2.3
20.7
1.90
65.0
8853
150
325
61/2.6
23.4
2.29
73.0
11240
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
2001~5000V One Core
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
8
7/1.2
3.6
2.29
14
244
300
14
7/1.6
4.8
2.29
16
330
300
22
7/2.0
6.0
2.29
17.5
448
300
38
7/2.6
7.8
2.29
19
644
300
60
19/2.0
10.0
2.29
21
897
300
100
19/2.6
13.0
2.29
25
1393
300
150
37/2.3
16.1
2.29
28.5
1950
300
200
37/2.6
18.2
2.29
30.5
2386
300
250
61/2.3
20.7
2.29
33.5
2987
200
325
61/2.6
23.4
2.29
36
3698
200
400
61/2.9
26.1
2.29
39
4510
200
500
61/3.2
28.8
2.29
41.5
5356
150
600
91/2.9
31.9
2.79
50
6678
150
800
127/2.8
36.4
2.79
55
8468
150
1000
127/3.2
41.6
2.79
60
10810
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
2001~5000V Three Cores
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
8
7/1.2
3.6
2.29
29
849
300
14
7/1.6
4.8
2.29
32
1246
300
22
7/2.0
6.0
2.29
34
1431
300
38
7/2.6
7.8
2.29
38
2077
300
60
19/2.0
10.0
2.29
42.5
2899
300
100
19/2.6
13.0
2.29
50.5
4514
300
150
37/2.3
16.1
2.29
57.5
6323
200
200
37/2.6
18.2
2.29
62
7659
150
250
61/2.3
20.7
2.29
68
9668
150
325
61/2.6
23.4
2.29
76
12220
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
5001~8000V One Core; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
14
7/1.6
4.8
2.92
17.5
391
300
22
7/2.0
6.0
2.92
19
491
300
38
7/2.6
7.8
2.92
20.5
693
300
60
19/2.0
10.0
2.92
23.5
1003
300
100
19/2.6
13.0
2.92
26.5
1456
300
150
37/2.3
16.1
2.92
30
2018
300
200
37/2.6
18.2
2.92
32
2460
200
250
61/2.3
20.7
2.92
35
3067
200
325
61/2.6
23.4
2.92
37.5
3782
150
400
61/2.9
26.1
2.92
40
4578
150
500
61/3.2
28.8
2.92
43
5452
150
600
91/2.9
31.9
4.45
52
6788
150
800
127/2.8
36.4
4.45
57
8587
150
1000
127/3.2
41.6
4.45
62.5
10940
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
5001~8000V Three Cores; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
14
7/1.6
4.8
2.92
34.5
1263
300
22
7/2.0
6.0
2.92
37
1590
300
38
7/2.6
7.8
2.92
41
2256
300
60
19/2.0
10.0
2.92
47
3274
300
100
19/2.6
13.0
2.92
53.5
4750
200
150
37/2.3
16.1
2.92
60.5
6586
150
200
37/2.6
18.2
2.92
65
8011
150
250
61/2.3
20.7
2.92
71
9970
150
325
61/2.6
23.4
2.92
79
12560
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
5001~8000V One Core; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
14
7/1.6
4.8
3.56
19
460
300
22
7/2.0
6.0
3.56
20
560
300
38
7/2.6
7.8
3.56
23
790
300
60
19/2.0
10.0
3.56
25
1065
300
100
19/2.6
13.0
3.56
28
1525
300
150
37/2.3
16.1
3.56
31
2095
300
200
37/2.6
18.2
3.56
34
2545
200
250
61/2.3
20.7
3.56
36
3155
200
325
61/2.6
23.4
3.56
39
3880
150
400
61/2.9
26.1
3.56
41.5
4680
150
500
61/3.2
28.8
3.56
46
5735
150
600
91/2.9
31.9
4.45
52
6915
150
800
127/2.8
36.4
4.45
57
8725
150
1000
127/3.2
41.6
4.45
62.5
11090
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
5001~8000V Three Cores; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
14
7/1.6
4.8
3.56
37.5
1500
300
22
7/2.0
6.0
3.56
40
1840
300
38
7/2.6
7.8
3.56
43.5
2450
300
60
19/2.0
10.0
3.56
49
3505
300
100
19/2.6
13.0
3.56
56
4990
200
150
37/2.3
16.1
3.56
63
6865
150
200
37/2.6
18.2
3.56
68.5
8320
150
250
61/2.3
20.7
3.56
74
10570
150
325
61/2.6
23.4
3.56
80
12930
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
8001~15000V One Core ; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
4.45
25
856
300
60
19/2.0
10.0
4.45
27
1130
300
100
19/2.6
13.0
4.45
30
1590
200
150
37/2.3
16.1
4.45
34
2167
200
200
37/2.6
18.2
4.45
36
2628
200
250
61/2.3
20.7
4.45
38
3246
200
325
61/2.6
23.4
4.45
41
3976
200
400
61/2.9
26.1
4.45
43.5
4785
150
500
61/3.2
28.8
4.45
48.5
5850
150
600
91/2.9
31.9
5.59
55
7021
150
800
127/2.8
36.4
5.59
59
8841
150
1000
127/3.2
41.6
5.59
65
11220
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
8001~15000V Three Cores; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
4.45
49.5
2840
200
60
19/2.0
10.0
4.45
54
3744
200
100
19/2.6
13.0
4.45
60.5
5084
150
150
37/2.3
16.1
4.45
68.5
7176
150
200
37/2.6
18.2
4.45
73
8441
150
250
61/2.3
20.7
4.45
80
10920
150
325
61/2.6
23.4
4.45
86
13310
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
8001~15000V One Core; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
5.59
27
964
200
60
19/2.0
10.0
5.59
29.5
1244
200
100
19/2.6
13.0
5.59
33
1721
150
150
37/2.3
16.1
5.59
36
2310
150
200
37/2.6
18.2
5.59
38
2767
150
250
61/2.3
20.7
5.59
40.5
3392
150
325
61/2.6
23.4
5.59
45
4130
150
400
61/2.9
26.1
5.59
47.5
5124
150
500
61/3.2
28.8
5.59
50
6031
150
600
91/2.9
31.9
5.59
55
7266
150
800
127/2.8
36.4
5.59
60
9013
150
1000
127/3.2
41.6
5.59
65
11500
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
8001~15000V Three Cores; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
5.59
54.5
3168
150
60
19/2.0
10.0
5.59
59
4098
150
100
19/2.6
13.0
5.59
66.5
5669
150
150
37/2.3
16.1
5.59
73
7606
150
200
37/2.6
18.2
5.59
80
9369
150
250
61/2.3
20.7
5.59
85
11420
150
325
61/2.6
23.4
5.59
91
13960
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
15001~25000V One Core; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
6.6
29.5
1060
300
60
19/2.0
10.0
6.6
32
1340
300
100
19/2.6
13.0
6.6
35
1850
200
150
37/2.3
16.1
6.6
38
2480
200
200
37/2.6
18.2
6.6
40
2940
200
250
61/2.3
20.7
6.6
42.5
3560
200
325
61/2.6
23.4
6.6
47
4500
200
400
61/2.9
26.1
6.6
50
5390
150
500
61/3.2
28.8
6.6
52
6300
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
15001~25000V Three Cores; Neutral Grounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
6.6
59
3520
200
60
19/2.0
10.0
6.6
64
4440
200
100
19/2.6
13.0
6.6
71
6100
150
150
37/2.3
16.1
6.6
80
8410
150
200
37/2.6
18.2
6.6
84
9930
150
250
61/2.3
20.7
6.6
89
11930
150
325
61/2.6
23.4
6.6
96
14480
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
15001~25000V One Core; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
8.76
34.5
1300
200
60
19/2.0
10.0
8.76
36.5
1590
200
100
19/2.6
13.0
8.76
39.5
2100
150
150
37/2.3
16.1
8.76
43
2740
150
200
37/2.6
18.2
8.76
46.5
3370
150
250
61/2.3
20.7
8.76
49
4060
150
325
61/2.6
23.4
8.76
51.5
4880
150
400
61/2.9
26.1
8.76
54
5740
150
500
61/3.2
28.8
8.76
57
6670
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.
XLPE Insulated and Polyvinyl Chloride Sheathed Cables (CV)
15001~25000V Three Cores; Neutral Ungrounded System
Conductor
Thickness of insulation
mm
Approx.
Overall Diameter
mm
Approx.
Weight
Kg/km
Standard
Length
M
Normative Cross Area
mm2
Number/ Diameter of Wires
No./mm
Outer Diameter
Approx.
mm
38
7/2.6
7.8
8.76
70
4380
150
60
19/2.0
10.0
8.76
76
5620
150
100
19/2.6
13.0
8.76
83
7280
150
150
37/2.3
16.1
8.76
90
9420
150
200
37/2.6
18.2
8.76
94
10980
150
250
61/2.3
20.7
8.76
99
13230
150
325
61/2.6
23.4
8.76
105
15850
150
For conductor area large than 8 mm2, both compressed and compact stranded conductors are available.